Single-phase input wire size

Sizing the 240V single-phase feeder from your service panel to the converter. Figures assume 240V, copper conductors, 75°C terminations and a run under about 100 ft.

Converter / motorApprox. input ampsBreakerCopper conductor
3 HP~20 A30 A10 AWG
5 HP~30 A40–50 A8 AWG
7.5 HP~44 A60 A6 AWG
10 HP~58 A70–80 A4 AWG
15 HP~85 A100 A3 AWG
20 HP~110 A125 A1 AWG
25 HP~135 A150 A1/0 AWG
30 HP~160 A175–200 A2/0 AWG

Notes for the input side

  • The converter draws its rated input current plus whatever your machines pull, so size for the total running load, not just the converter.
  • A disconnect within sight of the converter is required in most jurisdictions — plan for it in your layout.
  • Two hot legs plus an equipment grounding conductor. A neutral is only needed if you are feeding 120V circuits from a separate source.
  • Inrush on start-up is brief but large. If a correctly sized breaker nuisance-trips, ask us about breaker curve type before increasing the size.
  • For runs longer than about 100 ft, increase the conductor one size for every additional 100 ft to keep voltage drop under 3%.

Planning guidance only. Final sizing must come from your nameplate values and the National Electrical Code, applied by a licensed electrician.