Three-phase output wire size

Sizing the run from the converter to your sub-panel or machine. Figures assume 240V three-phase, copper conductors, 75°C terminations and a run under about 100 ft.

Converter / motorApprox. motor FLABreakerCopper conductor
3 HP~9.6 A15–20 A14 AWG
5 HP~15.2 A20–30 A12 AWG
7.5 HP~22 A30–40 A10 AWG
10 HP~28 A40–50 A10 AWG
15 HP~42 A50–60 A8 AWG
20 HP~54 A70 A6 AWG
25 HP~68 A80–90 A4 AWG
30 HP~80 A100 A3 AWG

Notes for the output side

  • Size from each machine's nameplate full load amps. Motor nameplates vary, so never assume the table value is exact for your machine.
  • Feeding several machines from a sub-panel? Size the feeder for the largest motor plus the running current of the others.
  • Identify the manufactured leg and keep it off 120V control circuits and single-phase transformers.
  • Each machine still needs its own overcurrent protection and disconnect as required by code.
  • For runs longer than about 100 ft, increase the conductor one size for every additional 100 ft to keep voltage drop under 3%.

Planning guidance only. Final sizing must come from your nameplate values and the National Electrical Code, applied by a licensed electrician.